35KV 630A European after connector.General 630A European after connector can be use together with the T Fore connector and some other back connector, it can be provide more branches, and they can not together with the bushing directly, cover the back protection cap on the end of the blanking cover.Features Provides a fully screened and fully submersible separable connection when mated with the proper bushing or plug.Can be used under the circumstances.Built-in capacitive test point to determine the circuit status or install a fault indicator.No minimum phase clearance requirements.Mounting can be vertical, horizontal, or any angle in between.Scope of Delivery 630A European after connector Adaptor,Conductor cable lug,Connect lug,Two head screw,Silicone Lubricant、Clearing Paper,Installation Instruction Sheet,Quality Certificate.

| Reference No. | Conductor cross section(mm²) | Stretch range over insulation(mm) | cable type | size of stress cone |
| DR HTT-35/630-50 | 50 | 31 | 26/35 | A |
| DR HTT-35/630-70 | 70 | 32.6 | 26/35 | B |
| DR HTT-35/630-95 | 95 | 34.2 | 26/35 | C |
| DR HTT-35/630-120 | 120 | 35.6 | 26/35 | C |
| DR HTT-35/630-150 | 150 | 37.2 | 26/35 | D |
| DR HTT-35/630-185 | 185 | 38.7 | 26/35 | E |
| DR HTT-35/630-240 | 240 | 41.1 | 26/35 | F |
| DR HTT-35/630-300 | 300 | 43.2 | 26/35 | G |
| DR HTT-35/630-400 | 400 | 46.4 | 26/35 | H |
| DR HTT-35/630-500 | 500 | 49.2 | 26/35 | I |
| DR HTT-35/630-630 | 630 | 52.5 | 26/35 | I |