Model Meaning
Conditions of Use
Product Characteristics
Technical Parameter
| Parameter Name | Specification / Value |
|---|---|
| Rated insulation voltage (V) | AC660 |
| Rated working voltage (V) | AC380V (AC400) |
| Rated current of horizontal busbar (A) | ≤4000A |
| Rated current of vertical busbar (A) | 1000A |
| Maximum current of draw-out circuit (A) | 400A |
| Rated frequency (Hz) | 50(60) |
| Peak withstand current of horizontal busbar (kA) | 105, 176 |
| Short time withstand current of horizontal busbar (kA/1S) | 50, 80 |
| Peak withstand current of vertical busbar (kA) | 105 |
| Short time withstand current of vertical busbar (kA/1S) | 50 |
| Rated power frequency withstand voltage (V/1min) | 2500 |
| Secondary power frequency withstand voltage (V/1min) | 2500 |
| Enclosure protection level | IP40 |
| Enclosure dimension (mm) | Width 600(800,1000) × Depth 800(1000) × Height 2200 |
| Effective height of functional unit (mm) | 1760 |
Switchgear and Draw-out Types
According to the purpose, it can be classified into: incoming cabinet, bus-tie cabinet, feeder cabinet (motor centralized control cabinet, lighting distribution cabinet), and reactive power compensation cabinet. According to the incoming method, it can be classified into four types: upper incoming and upper outgoing, upper incoming and lower outgoing, lower incoming and upper outgoing, and lower incoming and lower outgoing.
There are five specifications for draw-out unit height, all based on a unit height of 160mm: 1/2 unit, 1 unit, 3/2 unit, 2 unit and 3 unit in five sizes. Draw-out circuit current is 400A or below.
Outline and Installation Dimension of Switchgear
| Name of switchgear | Width (W) | Depth (D) | Height (H) | Cable outlet (FXG) |
|---|---|---|---|---|
| Incoming cabinet | 600、800、1000 | 800、1000 | 2200 | — |
| Bus-tie cabinet | 800、1000 | — | ||
| Feeder cabinet | 800、1000 | 200×400、400×400 | ||
| Draw-out cabinet | 800、1000 | 200×350、400×350 | ||
| Compensation cabinet | 800、1000 | — |
Mounting Dimension
Installation Diagram